From this point we could proceed with the model population.
And the main focus here is on constructability
and spec
requirements.
At this stage after conduit population we are
transferring
conduit schedule data to Revit so all the conduits have information inside.


Spaces around electrical equipment (width, depth, and height) (110.26(A) NFPA 70) and dedicated space to provide access to equipment (110.26 (E) NFPA 70 )
Conduit raceway routing and supports placement
Expansion, expansion-deflection or deflections fittings where necessary according to 300.7(B) NFPA 70
Seismic bracing requirements for MEP systems (ISAT)

Sleeves and blockouts (in line with structural drawings set)
Inslab conduits modeling following the rules:
- max 3 conduits in group
- 1 feet between groups
- 1 ¼ max size of inslab conduit
And many others